- Home
- Fuji Electric France
- Products & Solutions
- Sales Network
- Support
- Registered Users
[ Printer-friendly version ][ Send to friend ]

FCX-AII transmitters offer measuring ranges from 10 mmCW and 500 bar and are available for differential, gauge and absolute pressure. For specific apllications like petrochimistry, our differential pressure transmitters can be used for static pressure up to 1035 bar.
• ACCURACY : Standard : ± 0.065% of calibrated span
Optional : ± 0.04% of calibrated span
• Long term STABILITY : ± 0.1% of max. span / 10 yers
Micro capacitance silicon sensor
| Measuring cell The differential pressure is applied on the silicone sensor and changes the two capacitance values of the sensor. It is assembled floating in the measuring cell neck and improves the static pressure and temperature characteristics... ![]() |
![]() | |
Digital Indicator : Features :
| |
| Burnout current : In conformance with the recommendations of NAMUR NE 43, the output of the transmitter can be driven to a specific value should the transmitter experience an internal failure. The standard output signal limits are 3,2 to 22,5 mA. In case of a transmitter failure, the burnout direction can be down scaled (3,2 to 4 mA) or up scaled (20 to 22,5 mA), being programmable. ![]() | Maintenance functions : |


Based on our extensive silicon chip manufacturing experience,

. The indicator can be used to show the output signal in engineering units, as a percentage or as a current in mA (this is useful for flow indication on a differential pressure transmitter).